Menu

THƯƠNG HIỆU

Rờ Le Thời Gian Timer Omron 0.1s-1200h H3DK-S2

  • Tình trạng: Còn hàng
  • Hãng sản xuất: Omron
  • Mã thiết bị: H3DK-S2
  • Bảo hành: 12 Tháng
  • Xuất xứ: Indonesia
Giá liên hệ
Quý khách vui lòng liên hệ báo giá ưu đãi đối với số lượng lớn.
Rated power supply voltage 24 to 240 VAC 50/60 Hz
24 to 240 VDC Ripple 20% max.
Allowable voltage variable range 85 to 110% of the power supply voltage
Power consumption Approx. 6.6 VA (at 240 VAC)
Reset voltage 10% max. of rated supply voltage
Number of time ranges 8
Operation mode ON delay, Flicker ON start, Interval, One shot output
Control output (Type) Relay output (DPDT/ Time-limit SPDT and switchable SPDT (Time-limit/Instantaneous))
Control output (Contact output) Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC/0.5 A max. at 125 VDC
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Ambient temperature range Operating: -20 to 55 ℃ (with no icing)
Storage: -40 to 70 ℃ (with no icing)
Ambient humidity range Operating: 25 to 85%
Accuracy of operating time ±1% FS max. (±1% ±10 ms in a range of 1.2 s)
Setting error ±10% FS ±0.05 s max.
Influence of voltage ±0.5% FS max. (±0.5% ±10 ms in a range of 1.2 s)
Influence of temperature ±2% FS max. (±2% ±10 ms in a range of 1.2 s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min
Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltage Between power terminals: 5 kV
Between current carrying terminals and exposed non-current carrying metal parts: 5 kV
Noise immunity ±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Mulfunction: 4 kV, Destruction: 8 kV
Vibration resistance Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h
Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistance Destruction: 1,000 m/s2, 3 times each in 6 directions
Malfunction: 100 m/s2, 3 times each in 6 directions
Life expectancy (relay output) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Degree of protection IP30 (Terminal Block: IP20)
Connecting method Terminal blocks
Accessories User label
Weight Approx. 120 g