RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Additional Information
Current Type: AC
Electrical Durability:
Ue =< 440 V 10000 cycle
Ue = 500 … 690 V 8000 cycle
30 cycles per hour
Mechanical Durability:
25000 cycle
60 cycles per hour
Number of Poles: 3
Power Loss: 212 W
Product Main Type: SACE Emax 2
Product Name: Air Circuit Breaker
Product Type: Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
Rated Current (In): 2000 A
Rated Voltage (Ur): 690 V
Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui): AC 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 66 kA
(230 V AC) 66 kA
(380 V AC) 66 kA
(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 66 kA
(660 V AC) 66 kA
(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw):