Model | GF4-P | GF4-T | ||||
Appearance(mm) | ||||||
In Timer function |
Repeat accuracy |
|
||||
Variation due to voltage change |
||||||
Variation due to temperature change |
||||||
Insulation resistance | 100 MΩ Min. (at 500 V d.c) (between current – carrying terminal and exposed noncurrent – carrying metal parts, between power supply circuit and control output circuit) |
|||||
Dielectric strength | 2,000 V a.c 50 / 60 Hz for 1 minute (between current – carrying terminal and exposed noncurrent – carrying metal parts, between power supply circuit and control output circuit) |
|||||
Noise immunity | Square wave noise by simulator AC : ± 2 kV (between power supply terminal board) ± 500 V (between input terminal) |
|||||
Vibration | Mechanical durability : 10 to 55 Hz : 0.75 mm double amplitude Malfunction durability : 10 to 55 Hz : 0.5 mm double amplitude |
|||||
Shock | Mechanical durability : 300 m/s² (approx. 30 G) Malfunction durability : 100 m/s² (approx. 10 G) |
|||||
Life expectancy | Mechanical : 10,000,000 operations Min. Electrical : 100,000 operations Min. (250 V a.c 3 A) |
|||||
Weight | GF4 – P : 184 gms, GF4 – T : 168 gms (with adaptor), GF4 – P41S : 100 gms | |||||
Power supply | 100 – 240 V a.c 50 – 60 Hz | |||||
Power consumption | GF4 – T : 4.8 V A, GF4 – P : 6.2 V A (240 V a.c 60 Hz) | |||||
Reset / Inhibit | Reset by power OFF : Min. power OFF time : 0.5 s External reset or inhibit : Min. reset input signal width : 0.02 s |
|||||
Control output | SPDT : 250 V a.c 3 A cosØ = 1(resistive load) Open collector : 30 V d.c Max. 100 mA Max. |
|||||
Ambient temperature | Operating : -10 °C to 55 °C | |||||
Humidity | 35 to 85 % R.H. |